One-stream  air-heating  units  of  STD-300  type  are  applied  for  air  heating  in  industrial and agricultural premises, as well as in heating and ventilating systems of buildings, under the conditions of moderate (U) climate of the 3rdcategory of location as per GOST 15150-69. Air should have maximum permissible  concentration  of  chemically  active  materials  as  per  GOST  12.1.005-88,  dust  content  not more than 0,5 mg/m3 and no adhesive substances and fibrous materials.

Air-heating  units STD – 300  are  designated for operation  with  such  a  heat-transfer  agent  as  hot (superheated) water (for STD-300 based on calorifer of KSktype) or dry saturated steam (for STD-300Пbased on air-heater of  KPtype), having temperature not more than 190° Сand operating pressure not more than 1,2 MPa.

Heating units of STD-300 type (water) are manufactured in right-hand option – if to look at the unit from the side of an axial fan calorifer delivery pipes are located from the right side of the unit, and for lefthand one delivery pipes are located from the left side.

Heating units manufactured by «Concern Medved» haveprotective mesh, which protects electric motor from strokes and deformations, as well as prevents the unit from ingress of foreign objects. Forthe purpose of convenience there is a box for unit connecting to mains.

Specifications of air-heating unit STD-300 based on water calorifer of KSk type

Parameter value STD-300
Air capacity, m3/h
25000
Heat capacity, KW 312,61
Heat-transfer agent water
Temperature of heat-transfer agent, С°
at inlet, not less
at outlet, not more
95
70
Temperature of air, С°
at inlet, not less
at outlet, not more
0
36
Rated capacity of electric motor, KW 2,2
Synchronous speed, min-1
1000
Weight, kg 320

Specifications of air-heating unit STD-300P based on steam air-heater of KP type

Parameter value STD-300
Air capacity, m3/h
25000
Heat capacity, KW 387,36
Heat-transfer agent steam
Steam parameters, t?C/p MПа 150/0,48
Temperature of air, С°
at inlet, not less
at outlet, not more
0
44
Rated capacity of electric motor, KW 2,2
Synchronous speed, min-1
1000
Weight, kg 320

 

Overall dimensions of air-heating units STD-300

Overall dimensions of air-heating units STD-300

Overall dimensions of STD-300P based on steam air-heater of KP type